JH1005: DC Current Single Trip Alarm w/Loop Excitation
JH1025: DC Current Dual Trip Alarm w/Loop Excitation

  • 4/20mA Input Typical, Others Available

  • Provides 24V Power to Input Loop

  • Switch-Selectable HI/LO Trip Function

  • Adjustable Deadband Standard

  • Quick-Check Red/Green Output LEDs

  • Industry-Standard Pinouts (11-Pin Socket)

  • AC or DC Power Options

Models JH1005 and JH1025 provide 24Vdc loop excitation for a remote 2-wire transmitter, take the signal from that transmitter and provide relay contact HI/LO trip outputs. They also may be used with DC-powered "3-wire" sensors and transmitters whose supply currents do not exceed 25mA.

The alarm trip points are adjustable anywhere within the input range. Deadbands also are fully adjustable, from 0.25% to 100% of span. A slide switch, accessible through the top of the enclosure, selects HI or LO trip operation (on dual alarms, HI/HI, HI/LO or LO/LO). Red/green LEDs indicate alarm status.

Alarm contacts are rated at 5 amps, 230Vac or 30Vdc. Model JH1005 provides one set of DPDT relay contacts; Model JH1025, two SPDT relays. AC and DC power options are available.
 
ORDERING INFORMATION

Model Number:   Select JH1005 single-trip alarm or JH1025 dual-trip alarm. Add suffix –AC for AC power or –DC for DC power.
Input Range:   Select 4/20mA for use with 2-wire inputs, or any other range allowed by the "Input Capabilities" spec, below.
Trip Points:  

If you would like the trip points to be factory set, please specify the following for each trip point. Specify HI or LO trip, specify the setpoint and specify the amount of deadband required (or specify "minimum deadband").

Power:  

Specify 115Vac, 230Vac, 12Vdc or 24Vdc.

Relay Action:

Standard is Failsafe - the relay is energized under normal conditions and de-energizes upon alarm or upon loss of power. Thus, loss of power is seen as an alarm condition. Or specify Option R (Reverse Acting) – relay is normally not energized and energizes (pulls in) upon alarm trip. Failsafe is provided if not specified.

INSTALLATION AND CONNECTIONS

These alarms plug into any standard 11-pin circular ("octal") relay socket. JH Technology offers two sockets: DS011 for DIN-rail or surface mounting and ST011 for Snap-Track® mounting (see the Accessories page).
 
Pin connections are:
 
    Pin 1: 
Power (AC or, if DC power option, DC plus).
    Pin 2: 
24Vdc power to input transmitter. **
    Pin 3: 
Power (AC or, if DC power option, DC minus).
    Pin 4: 
Signal input plus.***
    Pin 5: 
Signal input minus.
    Pin 6: 
Setpoint 1 relay NO contact.*
    Pin 7: 
Setpoint 1 relay moving contact.*
    Pin 8: 
Setpoint 1 relay NC contact.*
    Pin 9:  Setpoint 2 relay NO contact.*
    Pin 10: 
Setpoint 2 relay moving contact.*
    Pin 11: 
Setpoint 2 relay NC contact.*

(*) Note: NO (normally open) and NC (normally closed) refer to the relay state when no power is applied. For Failsafe operation the NO contacts are closed under non-alarm conditions. The NC contacts close upon alarm and upon loss of power. The terms Setpoint 1 and Setpoint 2 refer to dual-trip alarms. For single-trip alarms, both sets of contacts respond to the one trip point.

(**) Note: For 2-wire loop, connect to the transmitter’s plus output terminal. For 3-wire transmitter, connect to transmitter’s plus power terminal.

(***) Note: For 2-wire loop, connect to the transmitter’s minus output terminal. For 3-wire transmitter, connect to the transmitter’s plus output terminal.

DETAILED SPECIFICATIONS

Voltage Input Capabilities:

50mV minimum span, +/-20V maximum input. Offset ranges are allowed. (Input Impedance: 200Kohms or greater.)

Current Input
Capabilities:

1mA minimum span, +/-25mA maximum input. Offset ranges are allowed. (Input Resistance: Varies with input range. Contact factory for details. 62 ohms for 4/20mA input.)
Input Excitation: 24Vdc regulated. 25mA max. current.

Relay Contacts:  

Single Alarm, one DPDT relay. Dual Alarm, two SPDT relays. Contacts rated 5 Amps resistive, 115/230Vac or 30Vdc. 1/8 HP max inductive load at 115/230Vac. Refer to instructions for contact protection when switching inductive loads.

Setpoint Adjustment:  

0% to 100% of range.

Deadband
Adjustment:

0.25% to 100% of range.

Response Time:  

Under 100 milliseconds.

Isolation:  

Power, 1,500Vac rms (2,100V peak). Input/Output, 1,000Vac rms (1,400V peak).

Guaranteed Operating Temperature:  

-10 to +60 deg. C (14 to 140 deg. F).

Temperature Stability:  

+/-0.02% of span per deg. C, or better.

Power Requirements:  

AC, 115 or 230Vrms, 50/60Hz, 2.5V-A.
DC, 12 or 24V, 2.5W.