www.techsales-nw.com

 telephone: 503-345-9710 .

 Home | Products | Industries | Product Lines | News & Events | Contacts

Products

Control & I/O Systems > Alarm Modules > JH Technology >




Control & I/O Systems Products Index
 
Control and
I/O Systems

Alarm Modules
Transformer IEDs
SOE Devices
I/O Modules
SCADA Software
 
 
Search for Products by keyword(s)

 


 

 

JH Technology
Accessories
 
Mounting
Hardware

 

Loop Power Supply Modules

  • Powers 4/20mA Loops, Strain Gauges, Sensors and more

  • Outputs from 1.5 to 30Vdc

  • Available Short-Circuit Protected Outputs

  • Uses Standard 8-Pin Socket

  • 115 or 230 AC Input Power

JH Technology power supply modules provide regulated and filtered DC supplies. Model JH9046 provides two adjustable voltage range options: 1.5 to 15V at 100mA max. load or 15 to 30V at 50mA. If specified on your order, the factory will adjust the output to your requirements.

JH9246 is a dual-output model designed with 4/20mA 2-wire transmitter loops in mind. Each module is capable of powering two such loops. Its two 24V outputs are isolated from each other, minimizing ground-loop concerns in multi-loop applications.

All three models are internally protected against failure due to short circuits. 115 and 230Vac power options are available.
 
ORDERING INFORMATION

Model JH9046-1  Normally factory-set at 5Vdc, If you prefer different settings, please specify on your order and the factory will do it at no extra charge. Also specify on your order if you require a 115VAC or 230VAC input source.
Model JH9046-2 Normally factory-set  at 24Vdc. If you prefer different settings, please specify on your order and the factory will do it at no extra charge. Also specify on your order if you require a 115VAC or 230VAC input source.
Model JH9246

Nonadjustable Output Fixed at 24Vdc (+/-4%). Specify on your order if you require a 115VAC or 230VAC input source.

INSTALLATION AND CONNECTIONS

These power supplies plug into any standard 8-pin circular ("octal") relay socket. JH Technology offers two sockets: DS008 for DIN-rail or surface mounting and ST008 for Snap-TrackŪ mounting (see the Accessories page).
 
Pin connections are:
 
    Pin 1: 
AC Power
    Pin 2: 
No connection
    Pin 3: 
AC Power
    Pin 4: 
No connection
    Pin 5: 
Output (+) Positive, Second Supply* (JH9246 Only)
    Pin 6: 
Output (-) Negative, Second Supply* (JH9246 Only)
    Pin 7: 
Output (+) Positive
    Pin 8: 
Output (-) Negative

(*) Notes: The "Second Supply" at Pins 5 & 6 are available on the Model JH9246 only. For the JH9046-1 and JH9046-2 there are no connections to Pins 5 & 6.

DETAILED SPECIFICATIONS

Model JH9046-1:

Adjustable from 1.5 to 15Vdc. Factory set at 5V unless otherwise specified on your order. Maximum load, 100mA.

Model JH9046-2:

Adjustable from 15 to 30Vdc. Factory set at 24V unless otherwise specified on your order. Maximum load, 50mA.

Model JH9246:  

Two independent, isolated outputs, each fixed at 24Vdc (23.0 To 25.0 Vdc). Maximum load, 25mA per output.

Isolation:  

Power, 1,500Vac rms (2,100V peak). Input/Output, 1,000Vac rms (1,400V peak).

Guaranteed
Operating Temperature:  

-10 to +60 deg. C (14 to 140 deg. F).

Temperature Stability:  

+/-0.02% of span per deg. C, or better.

Power Requirements:  

AC, 115 or 230Vrms, 50/60Hz, 2.5V-A.


Copyright 2003 - 2008, Technical Sales & Field Services Northwest, all rights reserved