JH4380P: Process Signal Isolator Module
-
Isolates
and Converts Standard DC Process Signals
-
Input
and Output Selections: 0/5V, 0/10V, 4/20mAdc
-
Quick-Check
Red/Green Output LEDs
-
Industry
Standard 8-Pin Socket Mounting
-
AC
or DC Power Options
|

|
Model JH4380P isolates and converts standard process signals. It
is useful for eliminating ground loops and noise problems as well as
for converting between 4/20mA loop currents and standard
instrumentation voltages. Clearly marked slide switches, accessible
through the top of the module, eliminate the need for instructions
and charts.
Red-green Quick-Check LEDs give a quick indication of the
relative output. Red is brighter at the low end, green at high,
while at mid-scale both are approximately equal. Red-only indicates
offscale low while green-only indicates offscale high.
Isolation to 1,000 Vac RMS is provided, with linearity better
than 0.05%. Low drift circuitry provides high accuracy and
stability. The input is filtered to minimize high-frequency noise
and transients. AC and DC power choices are available.
For a fully-rangeable DC transmitter see Model JH4380W.
For a fixed-range transmitter with additional options see Model JH4300.
For a low-cost 4/20mA isolator see Model JH4300C.
ORDERING INFORMATION
| Model
Number: |
Select
JH4380P-AC for AC power or JH4380P–DC for DC power. |
| Input
/ Output Ranges: |
Factory set
for 4/20mA input and 4/20mA output. If you wish different
settings please specify on your order. The factory will
set and calibrate it at no additional charge. |
| Power:
|
Specify 115Vac, 230Vac, 12Vdc or 24Vdc.
|
INSTALLATION AND CONNECTIONS
These transmitters plug into any standard 8-pin
circular ("octal") relay socket. JH Technology offers two
sockets: DS008 for DIN-rail or surface mounting and ST008 for
Snap-Track mounting.
Pin connections are:
Pin 1: Power (AC or, if DC power
option, DC plus).
Pin 2: No connection.
Pin 3: Power (AC or, if DC power
option, DC minus).
Pin 4: No connection.
Pin 5: Input Signal plus (+).
Pin 6: Input Signal minus (-).
Pin 7: Output Signal plus (+).
Pin 8: Output Signal minus (-).
DETAILED SPECIFICATIONS
|
Input Ranges:
(Switch Selectable)
|
0/5Vdc, 0/10Vdc, 4/20mAdc. |
| Input
Impedance: |
0/5Vdc, 200Kohm. 0/10Vdc,
400Kohm. 4/20mAdc, 60 ohms |
|
Output
Ranges:
(Switch Selectable)
|
0/5Vdc, 0/10Vdc, 4/20mAdc. |
| Output
Load Capability: |
Voltage outputs, 10mA max.
current (1,000 ohms at 10V). Current output, 24V
compliance (1,200 ohms at 20mA). |
|
Accuracy:
(when properly calibrated)
|
+/-0.1% of span
|
|
Adjustability:
|
Zero and span each are adjustable
approx. +/-15% of span.
|
|
Linearity:
|
+/-0.05% of span or better.
|
|
Response
Time:
|
Under 100 milliseconds.
|
|
Isolation:
|
Power, 1,500Vac rms (2,100V peak).
Input/Output (JH4300 only), 1,000Vac rms (1,400V peak).
|
|
Guaranteed
Operating Temperature:
|
-10 to +60 deg. C (14 to 140 deg. F).
|
|
Temperature
Stability:
|
+/-0.02% of span per deg. C, or
better.
|
|
Power
Requirements:
|
AC, 115 or 230Vrms, 50/60Hz, 2.5V-A.
DC, 12 or 24V, 2.5W.
|
|