www.techsales-nw.com

 telephone: 503-345-9710 .

 Home | Products | Industries | Product Lines | News & Events | Contacts

Products

Instrumentation > Signal Conditioners > JH Technology >




Instrumentation Products Index
 
Process & Machine
Instrumentation

Flow/Batch Controllers
Flow Computers
Process Indicators
Signal Conditioners
Oil on Water Sensors
Transmitters
Test Equipment
 
 
Search for Products by keyword(s)

 

 

 

 

 

 

JH Technology
Accessories
 
Mounting
Hardware
Power
Supplies

 


 

 

JH4410I: 2 Input Multiplier (A x B)
JH4420I: 2 Input Divider (A / B)

  • Multiply or Divide Two DC Inputs

  • Quick-Check Red/Green Output LEDs

  • Industry Standard 8-Pin Socket Mounting

  • Nonstandard Ranges Available

  • AC or DC Power Options

The JH4410/4420 Series offers DC outputs representing the product or quotient of two DC inputs. Input and output ranges need not be the same; for example, the inputs could be 0/10Vdc while the output could be 4/20mA. These are fixed-range devices, precisely calibrated to your specified ranges at the factory.

Red-green Quick-Check LEDs give a quick indication of the relative output. Red is brighter at the low end, green at high, while at mid-scale both are approximately equal. Red-only indicates offscale low while green-only indicates offscale high.

Input/output isolation is standard. (The inputs are not isolated from each other.) Available options include, AC or DC power choices and reverse-action Option RT (decreasing output with increasing input).
 
Standard calibration calculates the inputs and output on a percent-of-span basis. For example, for Output = AxB with a 4/20mA input range and 0/10V output range, if both inputs are at 50% (12mA) the output will be 25% (0.5 x 0.5 = 0.25), or 2.5 volts.

Nonstandard calibrations are available, including dissimilar input ranges and input-to-output offsets. We also are able to provide Output = (AxB)/C in one unit. Please contact us with your special requirements.
 
ORDERING INFORMATION

Model Number:   Select your model number from the list above. Add suffix –AC for AC power or –DC for DC power
Input Range:   Specify any DC voltage or current range allowed by the "Input Capabilities" spec, below.
Output Range:  

Specify any DC voltage or current range allowed by the "Output Capabilities" spec, below.

Power:  

Specify 115Vac, 230Vac, 12Vdc or 24Vdc.

Reverse-Acting Transmitter  
(decreasing output with increasing input): 

Specify option RT

Loop-Powered Output

4/20 mA "current sink" output stage for connection to devices whose inputs provide 24 Vdc loop excitation. Specify Option LPO.

INSTALLATION AND CONNECTIONS

These transmitters plug into any standard 8-pin circular ("octal") relay socket. JH Technology offers two sockets: DS008 for DIN-rail or surface mounting and ST008 for Snap-Track mounting.

Pin connections are:
 
    Pin 1: 
Power (AC or, if DC power option, DC plus).
    Pin 2: 
No connection.
    Pin 3: 
Power (AC or, if DC power option, DC minus).
    Pin 4: 
"B" Input Signal plus (+).
    Pin 5: 
"A" Input Signal plus (+)
    Pin 6: 
Input Signal Common (-).
    Pin 7: 
Output Signal plus (+).
    Pin 8: 
Output Signal minus (-).

DETAILED SPECIFICATIONS

Voltage Input Capabilities:

100mV minimum span, +/-20V maximum input. Offset ranges are allowed. (Input Impedance: 200kohms or greater.)

Input Current
Capabilities:

1mA minimum span, +/-100mA maximum input. Offset ranges are allowed. (Input Resistance: Varies with input range. Contact factory for details. 62 ohms for 4/20mA input.)

Voltage Output Capabilities:  

1 volt minimum output span, -10 to +15V absolute limit. Offset ranges are allowed. Maximum output load, 10mA (1Kohm at 10V output).

Current Output Capabilities:  

1mA minimum output span, 0 to +25mA absolute limit. Positive offsets are allowed, negative outputs are not. Output drive capability, 24V (1,200 ohms max. at 20mA output).

Accuracy (factory calibration):

+/-0.2% of span

Adjustability:  

Zero and span each are adjustable approx. +/-15% of span.

Response Time:  

Under 100 milliseconds.

Isolation:  

Power, 1,500Vac rms (2,100V peak). Input/Output 1,000Vac rms (1,400V peak). Note: The inputs are not isolated from each other.

Guaranteed Operating Temperature:  

-10 to +60 deg. C (14 to 140 deg. F).

Temperature Stability:  

+/-0.02% deg. C, or better.

Power Requirements:  

AC, 115 or 230Vrms, 50/60Hz, 2.5V-A. DC, 12 or 24V, 2.5W.


Copyright 2003 - 2008, Technical Sales & Field Services Northwest, all rights reserved