JH5140: 2 Input Multiplication (A x B)
JH5150: 2 Input Division (A / B)
-
Voltage
or Current Inputs and Outputs
-
Quick-Check
Red/Green Output LEDs
-
Nonstandard
Ranges Available
-
DIN-Rail
Mount, 1 Inch Wide
-
Unpluggable
Terminal Strip
-
AC
or DC Power Options
|

|
JH5140/JH5150 Multiply/Divide Transmitters respond to the product
or ratio of 2 DC inputs and provide a proportional, isolated DC
output.
Standard calibration calculates the inputs and outputs on a
percent-of-span basis. For example, in a JH5140 multiplying
transmitter with 4/20mA inputs and a 0/10V output, when both inputs
are at 12mA (50%) the output will be 2.5V (25%). The equation is:
0.5 x 0.5 = 0.25.
Nonstandard calibrations are available, including dissimilar
input ranges and input-to-output offsets. We also can, as a special,
create the function, Output = (A x B)/C. Contact us with your
requirements.
Red-green Quick-Check LEDs give a quick indication of the
relative output. Red is brighter at the low end, green at high,
while at mid-scale both are approximately equal. Red-only indicates
offscale low while green-only indicates offscale high.
Voltage or current inputs and outputs may be chosen: the input
and output ranges need not be the same. Available options include AC
and DC power choices and reverse-acting transmitter (decreasing
output with increasing input).
ORDERING INFORMATION
| Model
Number: |
Select from
the list above according to your input function. Add
suffix A (for example, JH5140A) for AC power, D for DC
power |
| Input
Range: |
Specify any
DC voltage or current range allowed by the "Input
Capabilities" spec, below. |
| Output
Range: |
Specify any DC voltage or current range allowed by the
"Output Capabilities" spec, below.
|
| Power:
|
Specify 115Vac, 230Vac, 12Vdc or 24Vdc.
|
Reverse-Acting
Transmitter
(decreasing output with increasing input): |
Change the last digit of the model number to 1 (for
example, JH5141A).
|
| Loop-Powered
Output: |
4/20mA "current sink" output stage for
connection to devices whose inputs provide 24Vdc loop
excitation. Change the last digit of the model number to 2
(for example, JH5142A).
|
| Urethane
Coating: |
Specify Option U.
|
INSTALLATION AND CONNECTIONS
JH5000 Series transmitters snap onto 35mm DIN
rail. Connections are made to the front-panel terminals. The
terminal strip unplugs to facilitate calibrating or replacing the
transmitter.
Connections to the 8 terminals (top to bottom)
are:
1: Input A (Positive).
2: Input Common (Negative).
3: Input B (Positive).
4: No connection.
5: Output plus.
6: Output minus.
7: Power (AC or, if DC power option, DC
plus).
8: Power (AC or, if DC power option, DC
minus).
DETAILED SPECIFICATIONS
|
Voltage Input
Capabilities:
|
100mV minimum
span, +/-20V maximum input. Offset ranges are allowed.
(Input Impedance: 200kohms or greater.) |
|
Input Current
Capabilities:
|
1mA minimum
span, +/-100mA maximum input. Offset ranges are allowed. |
|
Voltage
Output Capabilities:
|
1 volt
minimum output span, -10 to +15V absolute limit. Offset
ranges are allowed. Maximum output load, 10mA (1Kohm at
10V output). |
|
Current
Output Capabilities:
|
1mA minimum
output span, 0 to +25mA absolute limit. Positive offsets
are allowed, negative outputs are not. Output drive
capability, 24V (1,200 ohms max. at 20mA output). |
|
Accuracy
(factory calibration):
|
+/-0.2% of span. (For divider, input B
must be greater than 20% of span to achieve rated
accuracy.)
|
|
Adjustability:
|
Zero and span each are adjustable
approx. +/-15% of span.
|
|
Linearity:
|
+/-0.05% of span or better.
|
|
Response
Time:
|
Under 100 milliseconds.
|
|
Isolation:
|
3-way (Power/Input/Output) 1,500Vac
rms (2,100V peak).
|
|
Guaranteed
Operating Temperature:
|
-10 to +60 deg. C (14 to 140 deg. F).
|
|
Temperature
Stability:
|
+/-0.02% of span per deg. C, or
better.
|
|
Power
Requirements:
|
AC, 115 or 230Vrms, 50/60Hz, 2.5V-A.
DC, 12 or 24V, 2.5W.
|
|