JH6010I: AC Voltage Input,
Isolated
JH6010IR: AC Voltage Input, Isolated, w/ True RMS Response
JH6020I: AC Current Input, Isolated
JH6020IR: AC Current Input, Isolated, w/ True RMS Response
-
Input
Ranges from 50mV to 250Volts,
1mA to 5 Amps
-
Quick-Check
Red/Green Output LEDs
-
True-RMS
Response Available
-
Nonstandard
Ranges Available
-
AC
or DC Power Options
|

|
The JH6010I/6020I series provides an isolated DC output
proportional to an AC voltage or current input. Applications range
from power monitoring to millivolt-level AC signals from sensors.
Input/output isolation is standard to guard against shock hazards in
power measurements and against ground loop errors.
Accuracy is better than 0.5% of span. True-RMS models maintain
accuracy even with non-sinusoidal waveforms. (Standard models are
average-responding, calibrated for RMS sine wave response.)
Red-green Quick-Check LEDs give a quick indication of the
relative output. Red is brighter at the low end, green at high,
while at mid-scale both are approximately equal. Red-only indicates
off scale low while green-only indicates off scale high.
Available options include AC or DC power choices and
reverse-action Option RT (decreasing output with increasing input).
ORDERING INFORMATION
| Model
Number: |
Select from
the list above. Add suffix -AC for AC power or -DC for DC
power. |
| Input
Range: |
Specify any
AC voltage or current range allowed by the "Input
Capabilities" spec, below. |
| Output
Range: |
Specify any AC voltage or current range allowed by the
"Output Capabilities" spec, below.
|
| Power:
|
Specify 115Vac, 230Vac, 12Vdc or 24Vdc.
|
Reverse-Acting
Transmitter
(decreasing output with increasing input): |
Specify option RT
|
| Loop-Powered
Output: |
4/20 mA "current sink" output stage for
connection to devices whose inputs provide 24 Vdc loop
excitation. Specify Option LPO.
|
INSTALLATION AND CONNECTIONS
These transmitters plug into any standard 8-pin
circular ("octal") relay socket. JH Technology offers two
sockets: DS008 for DIN-rail or surface mounting and ST008 for
Snap-Track mounting.
Pin connections are:
Pin 1: Power (AC or, if DC power
option, DC plus).
Pin 2: No connection.
Pin 3: Power (AC or, if DC power
option, DC minus).
Pin 4: No connection.
Pin 5: AC signal input.
Pin 6: AC signal input.
Pin 7: Output plus.
Pin 8: Output minus.
APPLICATION NOTE – CURRENT TRANSFORMER INPUTS
When monitoring the output of a current transformer never use
current-input Model JH6020I. Unplugging the module will remove the
transformer’s secondary load, resulting in potentially damaging or
dangerous voltage spikes (up to several hundred volts).
Instead, use voltage-input Model JH6010I with an appropriate
precision external shunt resistor. For 0/5 amps we recommend
specifying a 0/250mVac input range with a 0.05 ohm, 0.1% 3 watt
external shunt. We offer Part No. R0.05/DS008, a precision shunt
resistor assembly pre-assembled to socket DS008. The socket snaps
onto DIN rail or may be surface mounted using screws.
DETAILED SPECIFICATIONS
|
Voltage Input
Capabilities:
(Model JH6010I)
|
50mV Vac minimum span, 250Vac maximum
input. Offset ranges are allowed. (Input Impedance:
200kOhms or greater.)
|
|
Input Current
Capabilities:
(Model JH6020I)
|
1mA- AC minumum span, 5 Amps
AC maximum input. Offset ranges are allowed. (Input
Resistance: Varies with input range. Contact factory for
details.
Caution - see application note above regarding
current transformer inputs. |
|
Input
Frequency:
|
40 Hz to 1kHz. For rated accuracy
|
|
Voltage
Output Capabilities:
|
1 volt minumum output span, -10 to
+15V absolute limit. Positive offsets are allowed. Maximum
output lowad, 10mA (1Kohm at 10V output).
|
|
Current
Output Capabilities:
|
1mA minimum output span, 1 to +25mA
absolute limit. Positive offsets are allowed, negative
outputs are not. Output drive capability, 24V (1,200 ohms
max. at 20mA output).
|
|
Accuracy
(factory calibration):
|
+/-0.02% of span per deg. C, or
better.
|
|
Adjustability:
|
Zero and span each are adjustable
approx. +/-15% of span.
|
|
Linearity:
|
+/-0.1% of span or better.
|
|
Response
Time:
|
Under 200 milliseconds.
|
|
Isolation:
|
Power, 1,500Vac rms (2,100V peak).
Input/Output, 1,000Vac rms (1,400V peak).
|
|
Guaranteed
Operating Temperature:
|
-10 to +60 deg. C (14 to 140 deg. F).
|
|
Temperature
Stability:
|
+/-0.02% of span per deg. C, or
better.
|
|
Power
Requirements:
|
AC, 115 or 230Vrms, 50/60Hz, 2.5V-A.
DC, 12 or 24V, 2.5W.
|
|