Monaghan Engineering ProTime SER |
The ProTime Sequence of Events Recorder is a distributed I/O module
that mounts on a standard DIN rail. Each module contains 32 inputs.
Up to 250 ProTime SER modules can be synchronized together to build
an event recording system with up to 8000 points. |
|

view enlarged
image |
|
The module communicates in Modbus® protocol over an RS-232 or
RS-485 connection. The ProTime module also contains a 10/100BaseT
Ethernet connection, which supports Modbus® TCP/IP.
The ProTime module combines the functions of an External Time
Reference interface device and a Sequence of Events Recorder device
into one module.
A ProTime SER module can receive its time synchronization from
another SER module, an IRIG-B time code signal or a direct interface
to a GPS300 GPS receiver. The ProTime
SER can also act as a time sync master to synchronize other SER
modules. Details >
Specifications
-
Inputs: 32 contacts, compression terminal
blocks or plugs
-
Input Voltage: 24, 48 or 125 Vdc
-
Power: 24, 48 or 125 VDC, 120 Vac
-
Event Memory: 6000 events
-
Operating Temperature: -20 C to +85 C
-
Humidity: 0 to 95% non-condensing
-
Communications: (view
diagram)
1 x RS-232 Modbus®
Port,
1 x RS-485 Modbus®
port,
1 x 10/100BaseT
Modbus® TCP port
-
Synchronization: (view
diagram)
IRIG-B Time Code
Signal,
GPS300 GPS
Receiver, or
another SER module
Point Configuration Parameters
Each of the 32 input points can be individually configured with the
included MS-Windows® based configuration tool, or via the customers
SCADA / HMI software package. The configuration parameters for each
input point include the following:
-
Contact Filter Time (0 - 65535ms)
-
Contact Debounce Time (0 -65535ms)
-
Chatter Count (0 - 255 per minute)
-
Scan Status (0 = On, 1 = Off)
-
Point Description (32 characters)
-
Off State Description (16 characters)
-
On State Description (16 characters)
Event Types
The ProTime SER module provides 1ms resolution time and date
stamped reporting for the following types of events:
-
Point Status Change
-
Point On Scan
-
Point Off Scan
-
Point Chatter On Scan
-
Point Chatter Off Scan
-
Power On Reset
-
RS-485 Time Sync Lock
-
RS-485 Time Sync Fail
-
Event Buffer Overflow
-
Time Re-Sync Old Time Value
-
Time Re-Sync New Time
-
Hourly Time Update
-
Time Re-Sync New Date
-
Reconfigure (the modules configuration
parameters have changed)
-
Restart Date
-
Restart Time
-
Power Fail
-
GPS Time Sync Lock
-
GPS Time Sync Fail
-
IRIG-B Time Sync Lock
-
IRIG-B Time Sync Fail
|
|
|
|
|